CTERISTICS |
U
160BS |
U
160BL |
U160BLP |
|
MECHANICAL
|
Minimum
Mechanical Failing Load ( KN) |
160 |
160 |
160 |
|
Impact
Strength (NM) |
45 |
45 |
45 |
|
Residual
Strength (%) |
>65 |
>65 |
>65 |
|
Mechanical
Routine test Load(KN) |
80 |
80 |
80 |
|
Thermal-Mechanical Performance(-30~+40
0C) (KN) |
96-104 |
96-104 |
96-104 |
|
DIMENSIONS
|
Diameter (
mm ) |
280 |
280 |
325 |
|
Spacing (
mm) |
146 |
170 |
170 |
|
Creepage
distance ( mm ) |
370 |
370 |
545 |
|
Metal
fitting size |
20 |
20 |
20 |
|
Galvanized
Coating (gr/cm2) |
0.06 (85µ) |
0.06 (85µ) |
0.06 (85µ) |
|
ELECTRICAL
|
Power
frequency withstand voltage (KV)-Dry ,1minute |
75 |
80 |
80 |
|
Power
frequency withstand voltage (KV)-Wet 1minute |
45 |
50 |
50 |
|
Dry
lightning impulse withstand voltage(V) |
120 |
120 |
145 |
|
Puncture
withstand voltage ( KV ) |
130 |
130 |
130 |
|
Max Radio
Interference Voltage(20KV,1MHz),(db) |
50 |
50 |
50 |
|
PACKING AND
SHIPPING DATA |
Approx. net
weight ( kg ) |
6.14 |
6.2 |
8.48 |
|
Nº of
insulators per crate |
7 |
6 |
4 |
|
Crate Dimensions (CM) |
29×29×103 |
29×29×98 |
33×33×64 |
|
Gross
weight per crate ( kg ) |
47.2 |
41.75 |
38.15 |
|
Nº of
insulators per pallet |
84 |
72 |
48 |
|
Pallet
Dimensions L×W×H (CM) |
100×100×136 |
100×100×136 |
70×105×160 |
|
Gross
weight per pallet ( kg ) |
578 |
513 |
470 |